康华大厦给排水消防设计

论文编号:GP020论文字数:12723,页数:42 附CAD图

摘 要

本工程建筑面积约4.5万平方米,。地下2层,地上20层办公综合楼。建筑总高度为 79.93 米。系一类高层民用建筑。地下两层为车库,1-3层为票据市场,4-15层为办公区,16-19层为宾馆,20层为餐厅。本次设计所需要解决的是建筑内的给水系统,污水系统,雨水系统,消防系统及热水系统的设计,满足人们日常生活的需求。本次设计需要解决主要问题是各系统的选型,各系统管道的布置与敷设及相关计算。水源:市政给水:室外管网水压0.10~0.28Mpa;给水管径DN300。

排水:雨水、污水均排入城市污水管网。市政管网雨、污水分流。暴雨强度等相关资料按江苏溧阳地区在设计手册上查找。

建筑条件:建筑物耐火等级一~二级; 火灾危险等级为中危险级。

设计内容:给水,热水,污水,废水,雨水,消防,自喷系统。

供水系统共分三个区,低区:地下室和商场部分即-2~4层为低区,由市政给水管网直接供水;中区:5~15层设一组变频水泵供水;高区:宾馆和餐厅部分16~20层,供入高位水箱再供给。水泵房设在地下室。水箱容积为100m3,采用不锈钢成品水箱。变频供水设备的供水流量按各区的设计秒流量,压力可保证顶层的供水压力不小于0.1MP

宾馆和办公楼部分设集中热水供应,热源为锅炉房提供的高温蒸汽,通过热交换器产生热水。热水主要供高区的宾馆和中区的办公楼,设计供水温度为60℃。

室外排水采用雨污分流制,室内排水废污分流。

消火栓系统在地下水泵房内设高区和中低区合用一套消防水泵,消防管道成环状布置,竖向以设备层一为界采用减压阀分区,减压阀阀后压力0.2Mpa,上下区静压均不超过1.00Mpa;5~10层采用减压型消火栓,以保证栓口压力不超过0.50MPa。

自喷系统在地下水泵房内设二台自喷给水泵,控制配水管压力不超过0.4Mpa并且满足火灾初期最不利点喷头的喷水压力。

关键词:给水;热水;污水;废水;雨水;消防;自喷系统

The drainage for Kanghua Building

Abstract

The project construction area of about 4.5 million square meters. 2 underground floor, ground floor, 20-storey office complex. Total building height of 79.93 meters. Department of a class of senior civil construction. Two floors underground garage, 1-3-tier market for the notes for the 4-15-storey office area for the hotel, 16-19th floor, 20th floor for the restaurant. The design needs to be addressed is the building’s water supply system, sewage system, water system, fire system and water system design to meet the needs of daily life. The design needs to solve the main problem is the system of selection, the system layout and the laying of pipelines and related calculations. Water: Municipal Water: outdoor pipe network water pressure 0.10 ~ 0.28Mpa; Water pipe diameter DN300. Drainage: rainwater and sewage are discharged into urban sewage pipe network. Rain municipal pipe network, sewage diversion. Storm intensity and other related information by Jiangsu Liyang area find in the design manual. Construction Conditions: The fire resistance level of 1 ~ 2 buildings; fire danger rating for the risk level. Design elements: water, water, sewage, waste water, rain, fire, since the spray system. The water supply system is divided into three areas, the low zone: part of the basement and shopping malls that -2 to 4 layers for the low zone, directly by the municipal water supply to the water supply network; Central District: 5 ~ 15 levels set a variable frequency pump water; High District: the apartments and the restaurant part of the 16 to 20 layers for the high water tank and then into the supply. Pump room in the basement. Tank volume of 100m3, finished with stainless steel water tank. Variable water flow rate of water supply equipment Design Flow of districts, the pressure can be guaranteed not less than the top of the water supply pressure 0.1MPa Hotel and office part of the set concentration of hot water, heat for the steam boiler to provide heat, hot water generated by heat exchanger. Water primarily for the high zone in the area of apartments and office buildings, the design water temperature is 60 ℃. Outdoor water use of rain and sewage diversion system, interior drain waste and sewage separation. Groundwater pumping station equipped with fire hydrant system in the high zone and low zone 2 fire pumps, fire pipeline into the ring arrangement, the vertical to the device layer is bounded by a valve area, after the regulator valve pressure 0.2Mpa, up and down District static pressure not more than 1.00Mpa; 5 ~ 10 layers of vacuum-type fire hydrants to ensure that population pressure does not exceed bolt 0.50MPa. Since the spray system in the groundwater pumping station equipped with two sets flowing to the pump, control with no more than 0.4Mpa water pressure and to meet the most unfavorable initial point of the fire sprinkler water spray pressure.

Key words: Water supply; water; water; wastewater; rain; fire; Automatic Sprinkler System

目 录

摘 要I

目 录V

1 设计说明书1

1.1设计计依据1

1.2设计内容1

1.3工程概况1

1.4设计用水量2

1.5水源和生活给水系统2

1.6热水系统2

1.7排水系统3

1.8雨水系统3

1.9消防系统4

1.10自动喷水系统5

1.11主要设备材料表5

1.12节能节水7

1.13环保专篇7

2 设计计算书8

2.1建筑概况:8

2.2设计依据:8

2.3给水系统:8

2.4排水系统:13

2.5消防系统:15

2.6自喷系统:19

2.7热水系统:23

2.8雨水系统:34

致 谢36

参考文献37

康华大厦给排水消防设计......